ISSN 1608-4039 (Print)
ISSN 1680-9505 (Online)


ресурсные испытания

Accelerated charge method of the lead-acid batteries. 1. Constant current stage of the charge

Strategy of the accelerated mode of the charge, including constant current charge to 80 % state-of-charge and a pulse charge by asymmetric current to a full charge is offered. Results of the first investigation phase devoted to studying of influence of a mode constant current charge on a resource of lead-acid accumulators are presented in this work. Various influence of size of an initial charge current on degradation of positive and negative active materials and possibility of charge of the accumulator to 80 % state-of-charge for 0.5 h is demonstrated.